Parameter Values (Range) Unit Step Default Description
5=off
A Hi high limit res 0.00...40.00 xIn 1 0.20 High alarm current
limit
A high limit res 0.00...40.00 xIn 1 0.05 High warning cur-
rent limit
A deadband res 100...100000 1 2500 Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Table 603: RESCMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement
mode
1=RMS
2=DFT
2=DFT Selects used meas-
urement mode
8.1.6.5 Monitored data
RESCMMXU Monitored data
Table 604: RESCMMXU Monitored data
Name Type Values (Range) Unit Description
Io-A FLOAT32 0.00...40.00 xIn Measured residu-
al current
BLOCK BOOLEAN
0=False
1=True
Block signal for
all binary out-
puts
HIGH_ALARM BOOLEAN
0=False
1=True
High alarm
HIGH_WARN BOOLEAN
0=False
1=True
High warning
I_INST_RES FLOAT32 0.00...40.00 xIn Residual current
Amplitude, mag-
nitude of instan-
taneous value
I_ANGL_RES FLOAT32 -180.00...180.00 deg Residual current
angle
I_DB_RES FLOAT32 0.00...40.00 xIn Residual current
Amplitude, mag-
nitude of repor-
ted value
I_DMD_RES FLOAT32 0.00...40.00 xIn Demand value of
residual current
Table continues on the next page
Measurement functions 1MRS758755 C
588 REC615 & RER615
Technical Manual