8.1.7 Residual voltage measurement RESVMMXU
8.1.7.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Residual voltage measurement RESVMMXU Uo Vn
8.1.7.2 Function block
Figure 297: Function block
8.1.7.3 Signals
RESVMMXU Input signals
Table 607: RESVMMXU Input signals
Name Type Default Description
Uo SIGNAL 0 Residual voltage
BLOCK BOOLEAN 0=False Block signal for all bi-
nary outputs
RESVMMXU Output signals
Table 608: RESVMMXU Output signals
Name Type Description
HIGH_ALARM BOOLEAN High alarm
HIGH_WARN BOOLEAN High warning
8.1.7.4 Settings
RESVMMXU Non group settings
Table 609: RESVMMXU Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
V Hi high limit res 0.00...4.00 xUn 1 0.20 High alarm voltage
limit
Table continues on the next page
Measurement functions 1MRS758755 C
590 REC615 & RER615
Technical Manual