EasyManua.ls Logo

ABB Relion REC615 - Page 607

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.1.12.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single-phase power and energy
measurement
SPEMMXU SP, SE SP, SE
8.1.12.2 Function block
Figure 302: Function block
8.1.12.3 Signals
Table 635: SPEMMXU Input signals
Name Type Default Description
RSTACM BOOLEAN 0=False Reset of accumulated
energy reading
8.1.12.4 Settings
Table 636: SPEMMXU Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Power unit Mult
3=k
6=M
3=k Unit multiplier for
presentation of the
power related val-
ues
Energy unit Mult
3=k
6=M
3=k Unit multiplier for
presentation of the
energy related val-
ues
Active power Dir
1=Forward
2=Reverse
1=Forward Direction of active
power flow: For-
ward, Reverse
Reactive power Dir
1=Forward
2=Reverse
1=Forward Direction of reac-
tive power flow:
Forward, Reverse
Table 637: SPEMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Forward Wh Initial 0...999999999 1 0 Preset Initial value
for forward active
energy
Reverse Wh Initial 0...999999999 1 0 Preset Initial value
for reverse active
energy
Table continues on the next page
1MRS758755 C Measurement functions
REC615 & RER615
Technical Manual
607