8.1.12.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single-phase power and energy
measurement
SPEMMXU SP, SE SP, SE
8.1.12.2 Function block
Figure 302: Function block
8.1.12.3 Signals
Table 635: SPEMMXU Input signals
Name Type Default Description
RSTACM BOOLEAN 0=False Reset of accumulated
energy reading
8.1.12.4 Settings
Table 636: SPEMMXU Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Power unit Mult
3=k
6=M
3=k Unit multiplier for
presentation of the
power related val-
ues
Energy unit Mult
3=k
6=M
3=k Unit multiplier for
presentation of the
energy related val-
ues
Active power Dir
1=Forward
2=Reverse
1=Forward Direction of active
power flow: For-
ward, Reverse
Reactive power Dir
1=Forward
2=Reverse
1=Forward Direction of reac-
tive power flow:
Forward, Reverse
Table 637: SPEMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Forward Wh Initial 0...999999999 1 0 Preset Initial value
for forward active
energy
Reverse Wh Initial 0...999999999 1 0 Preset Initial value
for reverse active
energy
Table continues on the next page
1MRS758755 C Measurement functions
REC615 & RER615
Technical Manual
607