9.5.5 Application
Figure 353: Application configuration example
A recommended application configuration example is described in
Figure 353
.
Undervoltage detection on bus 1 and undervoltage detection on bus 2 are
connected directly to the UN_U_BUS1 and UN_U_BUS2. The undervoltage indication
at each bus can be detected from for example functions PHPTUV, VMMXU or
PHSVPR.
Load fault detections on busbar, such as overcurrent and earth-fault functions are
connected as grouped protection input to BLOCK.
Auto mode OFF/ON
is connected
to input BLOCK.
Control functions
1MRS758755 C
696 REC615 & RER615
Technical Manual