EasyManua.ls Logo

ABB Relion REC670 - Meshed Network Without Parallel Line

ABB Relion REC670
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Only detailed network studies can determine the operating conditions under which the
highest possible fault current is expected on the line. In most cases, this current appears
during three-phase fault conditions. But also examine single-phase-to-earth and two-phase-
to-earth conditions.
Also study transients that could cause a high increase of the line current for short times. A
typical example is a transmission line with a power transformer at the remote end, which can
cause high inrush current when connected to the network and can thus also cause the
operation of the built-in, instantaneous, overcurrent protection.
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
UBase
) and (
SBase
).
OpMode
: This parameter can be set to
2 out of 3
or
1 out of 3
. The setting controls the
minimum number of phase currents that must be larger than the set operate current
IP>>
for
operation. Normally this parameter is set to
1 out of 3
and will thus detect all fault types. If the
protection is to be used mainly for multi phase faults,
2 out of 3
should be chosen.
IP>>
: Set operate current in % of
IBase
.
StValMult
: The operate current can be changed by activation of the binary input ENMULT to
the set factor
StValMult
.
IP>>MinEd2Set
: Minimum settable operate phase current level in % of IBase, for IEC 61850 Ed.
2 settings.
IP>>MaxEd2Set
: Maximum settable operate phase current level in % of IBase, for IEC 61850 Ed.
2 settings.
7.1.3.1 Meshed network without parallel line
M12915-9 v7
The following fault calculations have to be done for three-phase, single-phase-to-earth and
two-phase-to-earth faults. With reference to figure
39, apply a fault in B and then calculate the
current through-fault phase current I
fB
. The calculation should be done using the minimum
source impedance values for Z
A
and the maximum source impedance values for Z
B
in order to
get the maximum through fault current from A to B.
~
~
Z
A
Z
B
Z
L
A B
IED
I
fB
Fault
IEC09000022-1-en.vsd
IEC09000022 V1 EN-US
Figure 39: Through fault current from A to B: I
fB
Then a fault in A has to be applied and the through fault current I
fA
has to be calculated,
figure
40. In order to get the maximum through fault current, the minimum value for Z
B
and
the maximum value for Z
A
have to be considered.
Section 7 1MRK 511 358-UEN A
Current protection
102
Application manual

Table of Contents

Related product manuals