EQUATION1447 V1 EN-US (Equation 91)
and operation for phase-to-phase voltage under:
EQUATION1990 V1 EN-US (Equation 92)
The below described setting parameters are identical for the two steps (
n
= 1 or 2). Therefore,
the setting parameters are described only once.
Characteristicn
: This parameter gives the type of time delay to be used. The setting can be
Definite time
,
Inverse Curve A
,
Inverse Curve B
,
Prog. inv. curve
. The selection is dependent on
the protection application.
OpModen
: This parameter describes how many of the three measured voltages that should be
below the set level to give operation for step n. The setting can be
1 out of 3
,
2 out of 3
or
3 out
of 3
. In most applications, it is sufficient that one phase voltage is low to give operation. If
UV2PTUV shall be insensitive for single phase-to-earth faults,
2 out of 3
can be chosen. In
subtransmission and transmission networks the undervoltage function is mainly a system
supervision function and 3 out of 3 is selected.
Un<
: Set operate undervoltage operation value for step
n
, given as % of the parameter
UBase
.
The setting is highly dependent of the protection application. It is essential to consider the
minimum voltage at non-faulted situations. Normally this voltage is larger than 90% of
nominal voltage.
tn
: time delay of step
n
, given in s. This setting is dependent of the protection application. In
many applications the protection function shall not directly trip when there is a short circuit or
earth faults in the system. The time delay must be coordinated to the short circuit protections.
tResetn
: Reset time for step
n
if definite time delay is used, given in s. The default value is 25
ms.
tnMin
: Minimum operation time for inverse time characteristic for step
n
, given in s. When
using inverse time characteristic for the undervoltage function during very low voltages can
give a short operation time. This might lead to unselective trip. By setting
t1Min
longer than
the operation time for other protections such unselective tripping can be avoided.
ResetTypeCrvn
: This parameter for inverse time characteristic can be set to
Instantaneous
,
Frozen time
,
Linearly decreased
. The default setting is
Instantaneous
.
tIResetn
: Reset time for step
n
if inverse time delay is used, given in s. The default value is 25
ms.
kn
: Time multiplier for inverse time characteristic. This parameter is used for coordination
between different inverse time delayed undervoltage protections.
ACrvn
,
BCrvn
,
CCrvn
,
DCrvn
,
PCrvn
: Parameters to set to create programmable under voltage
inverse time characteristic. Description of this can be found in the technical reference manual.
CrvSatn
: When the denominator in the expression of the programmable curve is equal to zero
the time delay will be infinity. There will be an undesired discontinuity. Therefore, a tuning
parameter
CrvSatn
is set to compensate for this phenomenon. In the voltage interval Un<
down to
Un<
· (1.0 -
CrvSatn
/100) the used voltage will be:
Un<
· (1.0 -
CrvSatn
/100). If the
programmable curve is used this parameter must be calculated so that:
1MRK 511 358-UEN A Section 8
Voltage protection
177