Common base IED values for primary current
IBase
and primary voltage
UBase
are set in the
global base values for settings function GBASVAL. The
GlobalBaseSel
is used to select
GBASVAL for the reference of base values.
FTAQFVR used to protect a turbine:
Frequency during start-up and shutdown is normally not calculated, consequently the
protection function is blocked by CB position, parameter
CBCheck
enabled. If the generator
supply any load when CB is in open position e.g. excitation equipment and auxiliary services
this may be considered as normal condition and
CBCheck
is ignored when the load current is
higher then the set value of
CurrStartLevel
. Set the current level just above minimum load.
EnaVoltCheck
set to
Disable
.
tCont
: to be coordinated to the grid requirements.
tAccLimit
,
FreqHighLimit
and
FreqLowLimit
setting is derived from the turbine manufacturer's
operating requirements, note that
FreqLowLimit
setting must always be lower than the set
value of
FreqHighLimit
.
FTAQFVR used to protect a generator:
Frequency during start-up and shutdown is normally not calculated, consequently the
protection function is blocked by CB position, parameter
CBCheck
enabled.
CurrStartLevel
set to
Disable
.
EnaVoltCheck
set to
Enable
, voltage and frequency limits set according to the generators
manufacturer's operating requirements. Voltage and frequency settings should also be
coordinated with the starting values for over and underexcitation protection.
tCont
: to be coordinated to the grid requirements.
tAccLimit
,
FreqHighLimit
and
FreqLowLimit
setting is derived from the generator
manufacturer's operating requirements.
1MRK 511 358-UEN A Section 9
Frequency protection
197
Application manual