EasyManua.ls Logo

ABB Relion REC670 - Signals in Double-Breaker Arrangement

ABB Relion REC670
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
QB2OPTR (QB220OTR)(bay 1/sect.B2)
S2DC_OP
VPS2_DC
EXDU_BB
en04000497.vsd
QB2OPTR (QB220OTR)(bay n/sect.B2)
. . .
. . .
. . .
VPQB2TR(VQB220TR) (bay 1/sect.B2)
VPQB2TR(VQB220TR) (bay n/sect.B2)
VPDCTR (B2/B3)
EXDU_BB (bay n/sect.B2)
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
DCOPTR (B2/B3)
EXDU_BB (bay 1/sect.B2)
EXDU_DC (B2/B3)
IEC04000497 V1 EN-US
Figure 132: Signals from any bays in section B2 to a bus-section disconnector
13.4.6.3 Signals in double-breaker arrangement
M13542-80 v5
If the busbar is divided by bus-section disconnectors, the condition for the busbar
disconnector bay
no other disconnector connected to the bus-section
must be made by a
project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding signals from busbar B
are used.
Section 1 Section 2
A1A2_DC(BS)
B1B2_DC(BS)
DB_BUS DB_BUSDB_BUS DB_BUS
(WA1)A1
(WA2)B1 B2
A2
en04000498.vsd
IEC04000498 V1 EN-US
Figure 133: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
S1DC_OP All disconnectors on bus-section 1 are open.
S2DC_OP All disconnectors on bus-section 2 are open.
VPS1_DC The switch status of all disconnectors on bus-section 1 is valid.
VPS2_DC The switch status of all disconnectors on bus-section 2 is valid.
EXDU_BB No transmission error from double-breaker bay (DB) that contains the above
information.
These signals from each double-breaker bay (DB_BUS) are needed:
Section 13 1MRK 511 358-UEN A
Control
286
Application manual

Table of Contents

Related product manuals