EasyManua.ls Logo

ABB Relion REC670 - Page 308

ABB Relion REC670
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
t1=180
t1=150
t1=120
t1=90
t1=60
t1=30
IEC06000488_2_en.vsd
IEC06000488 V2 EN-US
Figure 152: Inverse time characteristic for TR1ATCC and TR8ATCC
The second time delay,
t2
, will be used for consecutive commands (commands in the same
direction as the first command). It can have a definite or inverse time characteristic according
to the setting
t2Use
(Constant/Inverse). Inverse time characteristic for the second time delay
follows the similar formulas as for the first time delay, but the
t2
setting is used instead of
t1
.
Line voltage drop
SEMOD159053-105 v6
The purpose with the line voltage drop compensation is to control the voltage, not at the
power transformer low voltage side, but at a point closer to the load point.
Figure
153 shows the vector diagram for a line modelled as a series impedance with the
voltage U
B
at the LV busbar and voltage U
L
at the load center. The load current on the line is I
L
,
the line resistance and reactance from the station busbar to the load point are R
L
and X
L
. The
angle between the busbar voltage and the current, is j. If all these parameters are known U
L
can be obtained by simple vector calculation.
Values for R
L
and X
L
are given as settings in primary system ohms. If more than one line is
connected to the LV busbar, an equivalent impedance should be calculated and given as a
parameter setting.
The line voltage drop compensation function can be turned
On
/
Off
by the setting parameter
OperationLDC
. When it is enabled, the voltage U
L
will be used by the Automatic voltage control
for tap changer function, TR1ATCC for single control and TR8ATCC for parallel control for
voltage regulation instead of U
B
. However, TR1ATCC or TR8ATCC will still perform the
following two checks:
1. The magnitude of the measured busbar voltage U
B
, shall be within the security range,
(setting
Umin
and
Umax
). If the busbar voltage falls-out of this range the line voltage drop
compensation calculations will be temporarily stopped until the voltage U
B
comes back
within the range.
2. The magnitude of the calculated voltage U
L
at the load point, can be limited such that it is
only allowed to be equal to or smaller than the magnitude of U
B
, otherwise U
B
will be used.
However, a situation where U
L
>U
B
can be caused by a capacitive load condition, and if the
wish is to allow for a situation like that, the limitation can be removed by setting the
parameter
OperCapaLDC
to
On
.
Section 13 1MRK 511 358-UEN A
Control
302
Application manual

Table of Contents

Related product manuals