EasyManua.ls Logo

ABB Relion REC670 - Identification; Application; Setting Guidelines; Generic Communication Function for Double Point Indication DPGAPC

ABB Relion REC670
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13.7.1 Identification
SEMOD167850-2 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Selector mini switch VSGAPC - -
13.7.2 Application
SEMOD158803-5 v6
Selector mini switch (VSGAPC) function is a multipurpose function used in the configuration
tool in PCM600 for a variety of applications, as a general purpose switch. VSGAPC can be used
for both acquiring an external switch position (through the IPOS1 and the IPOS2 inputs) and
represent it through the single line diagram symbols (or use it in the configuration through the
outputs POS1 and POS2) as well as, a command function (controlled by the PSTO input), giving
switching commands through the CMDPOS12 and CMDPOS21 outputs.
The output POSITION is an integer output, showing the actual position as an integer number 0
– 3.
An example where VSGAPC is configured to switch Autorecloser on–off from a button symbol
on the local HMI is shown in
figure 166. The I and O buttons on the local HMI are normally used
for on–off operations of the circuit breaker.
IEC07000112-3-en.vsd
PSTO
CMDPOS12
IPOS1
NAM_POS1
NAM_POS2
IPOS2
CMDPOS21
OFF
ON
VSGAPC
SMBRREC
ON
OFF
SETON
INTONE
INVERTER
INPUT
OUT
IEC07000112 V3 EN-US
Figure 166: Control of Autorecloser from local HMI through Selector mini switch
VSGAPC is also provided with IEC 61850 communication so it can be controlled from SA
system as well.
13.7.3 Setting guidelines
SEMOD158807-4 v4
Selector mini switch (VSGAPC) function can generate pulsed or steady commands (by setting
the
Mode
parameter). When pulsed commands are generated, the length of the pulse can be
set using the
tPulse
parameter. Also, being accessible on the single line diagram (SLD), this
function block has two control modes (settable through
CtlModel
):
Dir Norm
and
SBO Enh
.
13.8 Generic communication function for Double Point
indication DPGAPC
SEMOD55384-1 v4
Section 13 1MRK 511 358-UEN A
Control
334
Application manual

Table of Contents

Related product manuals