14.1.3.3 Permissive underreaching scheme
M13869-25 v4
Set
Operation
=
On
Set
SchemeType
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
Set
Unblock
=
Off
Set
tSecurity
= 0.035 s
14.1.3.4 Permissive overreaching scheme
M13869-34 v4
Set
Operation
=
On
Set
Scheme type
=
Permissive OR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Off
Set
tSecurity
= 0.035 s
14.1.3.5 Unblocking scheme
M13869-43 v4
Set
Unblock
=
Restart
(Loss of guard signal will give both trip and alarm
Choose
NoRestart
if only trip is required)
Set
tSecurity
= 0.035 s
14.1.3.6 Intertrip scheme
M13869-62 v4
Set
Operation
=
On
Set
SchemeType
=
Intertrip
Set
tCoord
50 ms (10 ms + maximal transmission time)
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Off
Set
tSecurity
= 0.015 s
14.2 Current reversal and Weak-end infeed logic for
distance protection 3-phase ZCRWPSCH
IP15751-1 v4
14.2.1 Identification
M15073-1 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end
infeed logic for distance protection
3-phase
ZCRWPSCH - 85
1MRK 511 358-UEN A Section 14
Scheme communication
347
Application manual