35kV Busbar
500/5
P Q
31,5 MVA
110/36,75/(10,5) kV
Yy0(d5)
U
L1L2
IEC09000040-1-en.vsd
IED
IEC09000040-1-EN V1 EN-US
Figure 188: Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 188, it is necessary to
do the following:
1. Set correctly all CT and VT and phase angle reference channel
PhaseAngleRef
(see section
"") data using PCM600 for analog input channels
2. Connect, in PCM600, measurement function to LV side CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the following
table
42:
Section 16 1MRK 511 358-UEN A
Monitoring
382