tTrCloseAlm
: Setting of alarm level for closing travel time.
OperAlmLevel
: Alarm limit for number of mechanical operations.
OperLOLevel
: Lockout limit for number of mechanical operations.
CurrExponent
: Current exponent setting for energy calculation. It varies for different types of
circuit breakers. This factor ranges from
0.5
to
3.0
.
AccStopCurr
: RMS current setting below which calculation of energy accumulation stops. It is
given as a percentage of
IBase
.
ContTrCorr
: Correction factor for time difference in auxiliary and main contacts' opening time.
AlmAccCurrPwr
: Setting of alarm level for accumulated energy.
LOAccCurrPwr
: Lockout limit setting for accumulated energy.
SpChAlmTime
: Time delay for spring charging time alarm.
tDGasPresAlm
: Time delay for gas pressure alarm.
tDGasPresLO
: Time delay for gas pressure lockout.
DirCoef
: Directional coefficient for circuit breaker life calculation.
RatedOperCurr
: Rated operating current of the circuit breaker.
RatedFltCurr
: Rated fault current of the circuit breaker.
OperNoRated
: Number of operations possible at rated current.
OperNoFault
: Number of operations possible at rated fault current.
CBLifeAlmLevel
: Alarm level for circuit breaker remaining life.
AccSelCal
: Selection between the method of calculation of accumulated energy.
OperTimeDelay
: Time delay between change of status of trip output and start of main contact
separation.
16.5 Event function EVENT
IP14590-1 v2
16.5.1 Identification
SEMOD167950-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function EVENT
S00946 V1 EN-US
-
16.5.2 Application
M12805-6 v9
When using a Substation Automation system with LON or SPA communication, time-tagged
events can be sent at change or cyclically from the IED to the station level. These events are