Settings for RS485 and optical serial communication
M17109-118 v10
General settings
SPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM optical serial port
while DNP and IEC 60870-5-103 only can utilize the RS485 port. A single protocol can be active
on a given physical port at any time.
Two different areas in the HMI are used to configure the IEC 60870-5-103 protocol.
1. The port specific IEC 60870-5-103 protocol parameters are configured under:
Main menu/Configuration/Communication/Station Communication/IEC6870-5-103/
• <config-selector>
• SlaveAddress
• BaudRate
• RevPolarity (optical channel only)
• CycMeasRepTime
• MasterTimeDomain
• TimeSyncMode
• EvalTimeAccuracy
• EventRepMode
• CmdMode
• RepIntermediatePos
<config-selector> is:
• “OPTICAL103:1” for the optical serial channel on the SLM
• “RS485103:1” for the RS485 port
2. The protocol to activate on a physical port is selected under:
Main menu/Configuration/Communication/Station Communication/Port
configuration/
• RS485 port
• RS485PROT:1 (off, DNP, IEC103)
• SLM optical serial port
• PROTOCOL:1 (off, DNP, IEC103, SPA)
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN-US
Figure 211: Settings for IEC 60870-5-103 communication
The general settings for IEC 60870-5-103 communication are the following:
•
SlaveAddress
and
BaudRate
: Settings for slave number and communication speed (baud
rate).
1MRK 511 358-UEN A Section 18
Station communication
427
Application manual