Table 12. Double-pole power output relays with TCS function
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at 48/110/220 V
DC (two contacts connected in series)
5 A/3 A/1 A
Minimum contact load 100 mA at 24 V AC/DC
Trip-circuit supervision (TCS):
Control voltage range 20...250 V AC/DC
Current drain through the supervision
circuit
~1.5 mA
Minimum voltage over the TCS contact 20 V AC/DC (15...20 V)
Table 13. Single-pole power output relays
Description
Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
Table 14. Front port Ethernet interfaces
Ethernet
interface
Protocol Cable Data transfer
rate
Front TCP/IP
protocol
Standard Ethernet CAT 5 cable with
RJ-45 connector
10 MBits/s
Motor Protection and Control 1MRS756890 D
REM615
Product version: 3.0 Issued: 2010-06-29