6.3.2 Configuring SMV with IET600
After the common configuration items have been completed, the SCD file has been
exported from PCM600 and the SCD file has been imported to IET600, the SMV
sender and receiver connections can be handled using the IET600 tool Ver.5.3.21 or
later.
1. In the Options dialog box in IET600, click Show IED Capabilities Tab.
GUID-28E4A3A2-8985-4C0D-B091-57B5031843B5 V1 EN
Figure 42: Selecting Show IED Capabilities Tab
2. In the IED Capabilities tab, check the Override for Client Service
SampledValues box to adjust the IED615 option to support sampled values
services.
1MRS757809 C Section 6
Process bus and IEEE 1588 time synchronization
REC615 and RER615 67
Engineering Guide