2.3.57 LD0.DARREC1 AR state (1)
Table 60: LD0.DARREC1 AR state (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DARREC1
2724 170.04 .AROn.stVal AR_ON AutoRecloser state 0/1=Off/On
2.3.58 LD0.DARREC1 Autorecloser (1)
Table 61: LD0.DARREC1 Autorecloser (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DARREC1
3040 190.00 .PrgRec.stVal INPRO AR in progess 1=In progress
3041 190.01 .mcd
3042 190.02 .PrgRec1.stVal INPRO_1 1st shot in progess 1=In progress
3043 190.03 .mcd
3044 190.04 .PrgRec2.stVal INPRO_2 2nd shot in progess 1=In progress
3045 190.05 .mcd
3046 190.06 .PrgRec3.stVal INPRO_3 3rd shot in progess 1=In progress
3047 190.07 .mcd
3048 190.08 .PrgRec4.stVal INPRO_4 4th shot in progess 1=In progress
3049 190.09 .mcd
3050 190.10 .PrgRec5.stVal INPRO_5 5th shot in progess 1=In progress
3051 190.11 .mcd
3052 190.12 .SucRec.stVal SUC_RECL Successful AR 1=Success
3053 190.13 .mcd
3054 190.14 .UnsRec.stVal UNSUC_RECL Unsuccessful AR 1=Unsuccess
3055 190.15 .mcd
3056 191.00 < reserved >
3057 191.01 < reserved >
3058 191.02 < reserved >
3059 191.03 < reserved >
3060 191.04 .LO.stVal LOCKED Lockout status 1=Lockout
3061 191.05 .mcd
3062 191.06 .RdyRec.stVal READY Reclose ready 1=Ready
3063 191.07 .mcd
3064 191.08 .ActRec.stVal ACTIVE Reclose active 1=Active
3065 191.09 .mcd
3066 191.10 .PrgDsr.stVal DISCR_INPRO Discr.time in progress 1=In progress
3067 191.11 .mcd
Table continues on next page
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 37
Point List Manual