GUID-2AE4D47A-2BBD-4422-A81C-CF2EB7473379 V1 EN
Figure 3: Signal wired to both OK and ALARM inputs – inverted to the other
If the OK and ALARM inputs are wired to separate indication
signals, the LED will have three legal states and cannot be
expressed with one bit only. In this case, it is possible to combine
this LED bit interpretation with the corresponding value from the
other LED state interpretation.
GUID-051741E8-4D66-412C-BA0A-0B849B5E58F2 V1 EN
Figure 4: Separate signals wired to OK and ALARM inputs
Table 82: LD0.LEDGGIO1 Indication LED states Color1/Color2
BitA
RegA IEC 61850 name SA name Description Values
LD0.LEDGGIO1
3520 220.00 .ISCSO1.stVal - LED 1 state 0/1=Color1/2
3521 220.01 .ISCSO2.stVal - LED 2 state 0/1=Color1/2
3522 220.02 .ISCSO3.stVal - LED 3 state 0/1=Color1/2
3523 220.03 .ISCSO4.stVal - LED 4 state 0/1=Color1/2
3524 220.04 .ISCSO5.stVal - LED 5 state 0/1=Color1/2
3525 220.05 .ISCSO6.stVal - LED 6 state 0/1=Color1/2
3526 220.06 .ISCSO7.stVal - LED 7 state 0/1=Color1/2
3527 220.07 .ISCSO8.stVal - LED 8 state 0/1=Color1/2
3528 220.08 .ISCSO9.stVal - LED 9 state 0/1=Color1/2
3529 220.09 .ISCSO10.stVal - LED 10 state 0/1=Color1/2
3530 220.10 .ISCSO11.stVal - LED 11 state 0/1=Color1/2
3531 220.11 <reserved> 0
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 49
Point List Manual