RegA Type Scale IEC 61850 name SA name Description Values
2009 u16 1000 .MaxAmpsA.mag Max demand IL1 - Max phsA demand
0.00...40.0
[xIn]
Update time stamp
1)
2010 u16 - - Year - month
2011 u16 - - Day - hour
2012 u16 - - Minute - second
2013 u16 - - Milliseconds
2014 u16 - - Time quality
2015 u16 1000 .MaxAmpsB.mag Max demand IL2 - Max phsB demand
0.00...40.0
[xIn]
Update time stamp
1)
2016 u16 - - Year - month
2017 u16 - - Day - hour
2018 u16 - - Minute - second
2019 u16 - - Milliseconds
2020 u16 - - Time quality
2021 u16 1000 .MaxAmpsC.mag Max demand IL3 - Max phsC demand
0.00...40.0
[xIn]
Update time stamp
1)
2022 u16 - - Year - month
2023 u16 - - Day - hour
2024 u16 - - Minute - second
2025 u16 - - Milliseconds
2026 u16 - - Time quality
1) See the technical manual.
2.4.33 CTRL.CBCSWI1 Circuit breaker operation counter (1)
Table 124: CTRL.CBCSWI1 Circuit breaker operation counter (1)
RegA
Type Scale IEC 61850 name SA name Description Values
CTRL.CBCSWI1
2027 u16 1 .OpCntRs.stVal Operation counter Operation counter 0…65535
1MRS757822 B Section 2
Modbus data mappings
Recloser Protection and Control RER615 67
Point List Manual