Name Type Values (Range) Unit Description
opening opera-
tion
T_TRV_CL FLOAT32 0...60000 ms Travel time of
the CB dur-
ing closing oper-
ation
T_SPR_CHR FLOAT32 0.00...99.99 s The charging
time of the CB
spring
NO_OPR INT32 0...99999 Number of CB
operation cycle
INA_DAYS INT32 0...9999 The number of
days CB has
been inactive
CB_LIFE_A INT32 -99999...99999 CB Remaining
life phase A
CB_LIFE_B INT32 -99999...99999 CB Remaining
life phase B
CB_LIFE_C INT32 -99999...99999 CB Remaining
life phase C
IPOW_A FLOAT32 0.000...30000.00
0
Accumulated
currents power
(Iyt), phase A
IPOW_B FLOAT32 0.000...30000.00
0
Accumulated
currents power
(Iyt), phase B
IPOW_C FLOAT32 0.000...30000.00
0
Accumulated
currents power
(Iyt), phase C
SSCBR Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
7.1.9 Technical data
Table 580: SSCBR Technical data
Characteristic Value
Current measuring accuracy
±1.5 % or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0 %
Table continues on the next page