EasyManua.ls Logo

ABB RELION REX640 - Web HMI

ABB RELION REX640
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 2 Relay engineering process
PCM600 is used for various tasks in the protection relay engineering process.
Relay engineering management
Organizing the bay protection relays in the structure of the substation by
defining voltage levels and bays below the substation. PCM600 manages
the project.
Configuring the protection relay functions (for example, protection and
control functions) by using Application Configuration
Configuring the parameters and setting values for the protection relay and
for the process functions by using Parameter Setting
Configuring LHMI pages, drawing single-line diagrams and making links
to dynamic process values by using Graphical Display Editor. The single-
line diagrams are displayed on the LHMI and the WHMI on the bay
protection relay.
Configuring connections between the application configuration function
blocks and physical hardware inputs and outputs by using Signal Matrix or
Application Configuration
Configuring the events shown on the LHMI using HMI Event Filtering
Communication management
IEC 61850 station communication engineering is done using the internal
IEC 61850 Configuration tool or the separate IET600. PCM600 interacts
with IET600 by importing and exporting SCL files.
Configuring the GOOSE receiving data connections to the protection
relay's application configuration function blocks by using the Application
Configuration tool and the Signal Matrix tool.
Configuring protocol data mapping for Modbus, DNP3 or IEC
60870-5-103 with the Communication Management tool.
Configuring the sampled values (process bus) between the devices using
Application Configuration, IEC 61850 Configuration and Signal Matrix.
Configuring Ethernet ports and other network settings using Ethernet
Configuration.
Record management
Generating overviews of the available disturbance recordings in all
connected protection relays by using Disturbance Handling
Manually reading the recording files (in the COMTRADE format) from the
protection relays by using Disturbance Handling or automatically by using
PCM600 Scheduler
Managing recording files with Disturbance Handling
1MRS759117 A Section 2
Relay engineering process
REX640 17
Engineering Manual

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals