Connections made with Signal Matrix are automatically shown in
Application Configuration.
GUID-BFACA61B-3AA4-4095-897C-BD6A2DEAE3CF V1 EN
Figure 61: Signal Matrix: a connection between binary input channels to binary
input signals
Each SMVRCV block used in Application Configuration needs to be connected to the
desired SMV stream in Signal Matrix. Connections need to be one-to-one and
unconnected SMVRCV blocks are not allowed.
Signal Matrix has a separate sheet for each possible combination.
Binary inputs
Binary outputs
Analog inputs
GOOSE
SMV
5.4 Load Profile tool
Load Profile tool is used for reading load profile records of COMTRADE format from
a protection relay, clearing old records and viewing records via an external
COMTRADE viewer. The default viewer included with PCM600 is Wavewin, but a
third-party viewer can be used.
1MRS759117 A Section 5
Protection and control engineering
REX640 83
Engineering Manual