EasyManua.ls Logo

ABB RELION REX640 - Page 1002

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Values (Range) Unit Description
-2=BCG Fault
-1=ABG Fault
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
Release PP-loop Enum
-5=No fault
-4=ABCG Fault
-3=CAG Fault
-2=BCG Fault
-1=ABG Fault
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
Release signals for
PP/3P loops. GFC
Cross country fault BOOLEAN
0=False
1=True
Indication of a cross-
country-fault (high imp.
earthed), GFC
Earth fault detected BOOLEAN
0=False
1=True
Indication of a single
phase earth-fault, GFC
Earth-fault direction Enum
0=unknown
1=forward
2=backward
3=both
Earth-fault direction
(low impedance earth-
ed), GFC
Operate of all zones INT32 0...31 Operate signal of all
zones
Fault/load Dir Zn1 Enum
0=unknown
1=forward
2=backward
3=both
Direction of fault or
load zone 1
Dir resistance Zn1 FLOAT32 -3000.00...3000.00 ohm Direction resistance,
zone 1
Dir reactance Zn1 FLOAT32 -3000.00...3000.00 ohm Direction reactance,
zone 1
Flt loop 1st Ris Zn1 FLOAT32 -3000.00...3000.00 ohm First PE-loop resist-
ance, zone 1
Flt loop 1st Rea Zn1 FLOAT32 -3000.00...3000.00 ohm First PE-loop reactance,
zone 1
Flt loop 2nd Ris Zn1 FLOAT32 -3000.00...3000.00 ohm Second PE-loop resist-
ance, zone 1
Flt loop 2nd Rea Zn1 FLOAT32 -3000.00...3000.00 ohm Second PE-loop reac-
tance, zone 1
Flt PP-loop Ris Zn1 FLOAT32 -3000.00...3000.00 ohm PP-loop resistance,
zone 1
Flt PP-loop Rea Zn1 FLOAT32 -3000.00...3000.00 ohm PP-loop reactance, zone
1
Table continues on the next page
Protection functions 1MRS759142 F
1002 REX640
Technical Manual

Table of Contents