Parameter Values (Range) Unit Step Default Description
2=Element counter
Start value 0.01...1.00 xIn 0.01 0.10 Start value
Alarm start value 0.01...1.00 xIn 0.01 0.05 Alarm start value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier
in IEC/ANSI IDMT
curves
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time Selection of time
delay curve type
Operate delay time 50...200000 ms 10 5000 Operate delay time
Alarm delay time 50...200000 ms 10 200000 Alarm delay time
Table 1071: CUBPTOC Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Fuse location
1=Internal
2=External
1=Internal Location of capaci-
tor fuse
Element fail limit 1...100 1 3 Element failure lim-
it above which
alarm is active
Natural Comp ena-
ble
0=False
1=True
0=False Enable natural un-
balance compensa-
tion
Table 1072: CUBPTOC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Curve parameter A 0.00860...120.0000
0
0.00001 28.20000 Parameter A for
customer program-
mable curve
Curve parameter B 0.00000...0.71200 0.00001 0.12170 Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00 0.01 2.00 Parameter C for
customer program-
mable curve
Curve parameter E 0.0...1.0 0.1 1.0 Parameter E for
customer program-
mable curve
1MRS759142 F Protection functions
REX640
Technical Manual
1129