Table 1144: ESMGAPC Monitored data
Name Type Values (Range) Unit Description
T_ST_EMERG Timestamp Emergency start activa-
tion timestamp
ESMGAPC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.6.10 Technical data
Table 1145: ESMGAPC Technical data
Characteristic Value
Operation accuracy At the frequency f = f
n
±1.5 % of the set value or ±0.002 × U
n
5.6.11 Technical revision history
Table 1146: ESMGAPC Technical revision history
Product
connectivi
ty level
Technical
revision
Change
PCL4 E Setting
Motor standstill A
minimum value changed from 0.05xIn
to 0.01xIn.
5.7 Fault locator SCEFRFLO (ANSI FLOC)
5.7.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fault locator SCEFRFLO FLOC FLOC
1MRS759142 F Protection related functions