Parameter Values (Range) Unit Step Default Description
Current dead Lin
Val
0.01...1.00 xIn 0.01 0.20 Dead line value,
current. Used also
in auto activation
logic
Voltage dead Lin
Val
0.01...0.58 xUn 0.01 0.40 Dead line value,
voltage. Used also
in auto activation
logic
Cur voltage Det
time
0...60000 ms 10 20 Time delay for volt-
age and current
based detection
Operate time delay 0...120000 ms 10 20 Delay for the de-
layed start input
SOTF reset time 0...60000 ms 10 1000 SOTF detection pe-
riod after initializa-
tion
Dead line time 0...60000 ms 10 200 Delay time for acti-
vation of dead line
detection
5.8.9 CVPSOF Monitored data
Table 1173: CVPSOF Monitored data
Name Type Values (Range) Unit Description
CVPSOF Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS759142 F Protection related functions
REX640
Technical Manual
1229