7.5.8 Settings
7.5.8.1 DGMGAPC Settings
Table 1351: DGMGAPC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Disable Fuel Crl
0=False
1=True
0=False Disable correlation
algorithm for fuel-
ing faults
Disable Fuel voting
0=False
1=True
0=False Disable voting al-
gorithm for fueling
faults
Disable Ext Crl
0=False
1=True
0=False Disable correlation
algorithm for exci-
tation faults
Disable Ext voting
0=False
1=True
0=False Disable voting al-
gorithm for excita-
tion faults
Disable Fuel Rck
Mon
0=False
1=True
0=False Disable fuel rack
position monitor-
ing
Disable Ext Cur
Mon
0=False
1=True
0=False Disable excitation
current monitoring
Min Freq limit 0.95...1.00 xFn 0.01 0.95 Minimum Freq lim-
it below which
STOP_ENGINE is ac-
tivated
Max Freq limit 1.00...1.05 xFn 0.01 1.05 Maximum Freq lim-
it above which
STOP_ENGINE is ac-
tivated
Min voltage limit 0.5...1.5 xUn 0.1 0.8 Minimum voltage
limit below which
DE_EXCITE is acti-
vated
Max voltage limit 0.5...1.5 xUn 0.1 1.2 Maximum voltage
limit above which
DE_EXCITE is acti-
vated
Operate delay time 10...300000 ms 10 600 Operate delay time
Max CB trip delay 10...300000 ms 10 600 Maximum time de-
lay for detection of
CB status
Disable time 10...3600000 ms 10 60000 Function disable
time during engine
loading/unloading
Backup delay time 10...300000 ms 10 100 Operate delay time
for backup protec-
tion
Table 1352: DGMGAPC Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Min active power 0.01...1.00 xSn 0.01 0.05 Active power lim-
it below which
STOP_ENGINE is ac-
tivated
Max active power 0.10...2.00 xSn 0.01 1.00 Active power lim-
it above which
STOP_ENGINE is ac-
tivated
Table continues on the next page
Condition monitoring functions 1MRS759142 F
1424 REX640
Technical Manual