Name Type Values (Range) Unit Description
SBNW_GEN6 INT32 0...8 Subnetwork number of
generator 6
SBNW_GEN7 INT32 0...8 Subnetwork number of
generator 7
SBNW_GEN8 INT32 0...8 Subnetwork number of
generator 8
SBNW_TIE_CB1 INT32 0...8 Subnetwork number of
tie breaker 1
SBNW_TIE_CB2 INT32 0...8 Subnetwork number of
tie breaker 2
SBNW_TIE_CB3 INT32 0...8 Subnetwork number of
tie breaker 3
SBNW_TIE_CB4 INT32 0...8 Subnetwork number of
tie breaker 4
SBNW_TIE_CB5 INT32 0...8 Subnetwork number of
tie breaker 5
SBNW_TIE_CB6 INT32 0...8 Subnetwork number of
tie breaker 6
SBNW_TIE_CB7 INT32 0...8 Subnetwork number of
tie breaker 7
SBNW_TIE_CB8 INT32 0...8 Subnetwork number of
tie breaker 8
DGMGAPC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
7.5.10 Technical data
Table 1356: Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured
voltage and current: f
n
±2 Hz
Voltage:
±1.5% of the set value or 0.002 xU
n
Frequency:
±5 mHz
Active power:
±3% of the set value or 0.002 xS
n
Reactive power:
±3% of the set value or 0.002 xS
n
Operate time accuracy ±1.0% of the set value or ±20 ms
Reset ratio Typically 0.96/1.04
Condition monitoring functions 1MRS759142 F
1432 REX640
Technical Manual