ABB RELION REX640 - 3.9.4 Signals; 3.9.4.1 FLTRFRC Input signals; 3.9.5 Settings; 3.9.5.1 FLTRFRC Settings

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 85: Special conditions
Condition Description
URES1
connected to the cal-
culated residual voltage
The function requires that all three voltage channels are con-
nected to UTVTR. Setting
VT connection
must be "Wye" in
that particular UTVTR.
URES2
connected to the cal-
culated residual voltage
The function requires that all three voltage channels are con-
nected to UTVTR. Setting
VT connection
must be "Wye" in
that particular UTVTR.
URES3
connected to the cal-
culated residual voltage
The function requires that all three voltage channels are con-
nected to UTVTR. Setting
VT connection
must be "Wye" in
that particular UTVTR.
3.9.4 Signals
3.9.4.1 FLTRFRC Input signals
Table 86: FLTRFRC Input signals
Name Type Default Description
I3P1 SIGNAL - Three-phase currents
1
I3P2 SIGNAL - Three-phase currents
2
I3P3 SIGNAL - Three-phase currents
3
IRES1 SIGNAL - Residual current 1
IRES2 SIGNAL - Residual current 2
IRES3 SIGNAL - Residual current 3
U3P1 SIGNAL - Three-phase voltages
1
U3P2 SIGNAL - Three-phase voltages
2
U3P3 SIGNAL - Three-phase voltages
3
URES1 SIGNAL - Residual voltage 1
URES2 SIGNAL - Residual voltage 2
URES3 SIGNAL - Residual voltage 3
3.9.5 Settings
3.9.5.1 FLTRFRC Settings
Basic functions
1MRS759142 F
146 REX640
Technical Manual