PEMMXU Input signals
Table 1431: PEMMXU Input signals
Name Type Default Description
I3P SIGNAL - Three-phase currents
U3P SIGNAL - Three-phase voltages
RSTACM BOOLEAN 0=False Reset of accumulated
energy reading
PEMMXU Output signals
Table 1432: PEMMXU Output signals
Name Type Description
S_INST FLOAT32 Apparent power, magnitude
of instantaneous value in kVA
P_INST FLOAT32 Active power, magnitude of
instantaneous value in kW
Q_INST FLOAT32 Reactive power, magnitude of
instantaneous value in kvar
PF_INST FLOAT32 Power factor, magnitude of
instantaneous value
EAFPULSE SIGNAL Accumulated forward active
energy pulse
EARPULSE SIGNAL Accumulated reverse active
energy pulse
ERFPULSE SIGNAL Accumulated forward reac-
tive energy pulse
ERRPULSE SIGNAL Accumulated reverse reactive
energy pulse
S_DMD FLOAT32 Demand value of apparent
power
P_DMD FLOAT32 Demand value of active pow-
er
Q_DMD FLOAT32 Demand value of reactive
power
PF_DMD FLOAT32 Demand value of power fac-
tor
8.1.13.6 PEMMXU Settings
Table 1433: PEMMXU Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
1=on Operation Off / On
Table continues on the next page
1MRS759142 F Measurement functions
REX640
Technical Manual
1483