Table 1435: PEMMXU Monitored data
Name Type Values (Range) Unit Description
S-kVA:1 FLOAT32 -999999.9...999999.9 kVA Total Apparent Power
P-kW:1 FLOAT32 -999999.9...999999.9 kW Total Active Power
Q-kVAr:1 FLOAT32 -999999.9...999999.9 kVAr Total Reactive Power
PF:1 FLOAT32 -1.00...1.00 Average Power factor
RSTACM BOOLEAN
0=False
1=True
Reset of accumulated
energy reading
S_INST FLOAT32 -999999.9...999999.9 kVA Apparent power, mag-
nitude of instantaneous
value
S_DB FLOAT32 -999999.9...999999.9 kVA Apparent power, mag-
nitude of deadband val-
ue
S_DMD FLOAT32 -999999.9...999999.9 kVA Demand value of appa-
rent power
P_INST FLOAT32 -999999.9...999999.9 kW Active power, magni-
tude of instantaneous
value
P_DB FLOAT32 -999999.9...999999.9 kW Active power, magni-
tude of deadband value
P_DMD FLOAT32 -999999.9...999999.9 kW Demand value of active
power
Q_INST FLOAT32 -999999.9...999999.9 kVAr Reactive power, magni-
tude of instantaneous
value
Q_DB FLOAT32 -999999.9...999999.9 kVAr Reactive power, magni-
tude of deadband value
Q_DMD FLOAT32 -999999.9...999999.9 kVAr Demand value of reac-
tive power
PF_INST FLOAT32 -1.00...1.00 Power factor, magni-
tude of instantaneous
value
PF_DB FLOAT32 -1.00...1.00 Power factor, magni-
tude of deadband value
PF_DMD FLOAT32 -1.00...1.00 Demand value of power
factor
EA_RV_ACM INT64 0...999999999 kWh Accumulated reverse
active energy value
ER_RV_ACM INT64 0...999999999 kVArh Accumulated reverse re-
active energy value
EA_FWD_ACM INT64 0...999999999 kWh Accumulated forward
active energy value
ER_FWD_ACM INT64 0...999999999 kVArh Accumulated forward
reactive energy value
Max demand S FLOAT32 -999999.9...999999.9 kVA Maximum demand val-
ue of apparent power
Min demand S FLOAT32 -999999.9...999999.9 kVA Minimum demand value
of apparent power
Max demand P FLOAT32 -999999.9...999999.9 kW Maximum demand val-
ue of active power
Min demand P FLOAT32 -999999.9...999999.9 kW Minimum demand value
of active power
Max demand Q FLOAT32 -999999.9...999999.9 kVAr Maximum demand val-
ue of reactive power
Min demand Q FLOAT32 -999999.9...999999.9 kVAr Minimum demand value
of reactive power
Time max dmd S Timestamp Time of maximum de-
mand
Time min dmd S Timestamp Time of minimum de-
mand
Table continues on the next page
1MRS759142 F Measurement functions
REX640
Technical Manual
1485