Earthing
contact
Disconnector
contact
Sliding part
Fixed contact
Insulang spindle
Protecon relay
RIO600
Motor
Motor control
Commands
Status
Posion contacts
Reed contact
Reed contact
Figure 838: Connection diagram for RIO600 control of a three-position switchgear
motor
When the RIO600 SCM module is selected as control mode, outputs
EXE_DCCLOSE, EXE_DCOPEN, EXE_ESCLOSE and EXE_ESOPEN are
connected in Application Configuration. When direct motor control is
selected as control mode, static outputs H_UP_LEFT, H_UP_RIGHT,
H_LO_LEFT and H_LO_RIGHT are connected in Application Configuration.
9.2.6 Signals
9.2.6.1 P3SXSWI Input signals
Table 1479: P3SXSWI Input signals
Name
Type Default Description
DCPOSOPEN BOOLEAN 0=False Signal for open posi-
tion of disconnector
DCPOSCLOSE BOOLEAN 0=False Signal for close posi-
tion of disconnector
Table continues on the next page
1MRS759142 F Control functions
REX640
Technical Manual