Table 1489: P3SSXSWI Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Event delay 0...60000 ms 1 10000 Event delay of in-
termediate or faul-
ty position
Vendor 0 External equipment
vendor
Serial number 0 External equipment
serial number
Model 0 External equipment
model
9.3.8 P3SSXSWI Monitored data
Table 1490: P3SSXSWI Monitored data
Name Type Values (Range) Unit Description
POSITION Enum
0=earthing switch
closed
1=earthing switch inter-
mediate
2=both open
3=disconnector inter-
mediate
4=disconnector closed
5=faulty
3-position switch posi-
tion
POSITION_DC Dbpos
0=intermediate
1=open
2=closed
3=faulty
Disconnector position
POSITION_ES Dbpos
0=intermediate
1=open
2=closed
3=faulty
Earthing switch posi-
tion
9.4 Disconnector position indicator DCSXSWI and
Earthing switch position indication ESSXSWI (ANSI
29DS, 29GS)
9.4.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Disconnector position indication DCSXSWI I<->O DC 29DS
Earthing switch indication ESSXSWI I<->O ES 29GS
1MRS759142 F Control functions
REX640
Technical Manual
1539