ABB RELION REX640 - 9.10.8 OL5 ATCC Settings

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Description
FLLW1_CTL INT32 Lower/Raise command for
follower transformer 1 in
the Master/Follower opera-
tion mode
FLLW2_CTL INT32 Lower/Raise command for
follower transformer 2 in
the Master/Follower opera-
tion mode
FLLW3_CTL INT32 Lower/Raise command for
follower transformer 3 in
the Master/Follower opera-
tion mode
FLLW4_CTL INT32 Lower/Raise command for
follower transformer 4 in
the Master/Follower opera-
tion mode
FLLW5_CTL INT32 Lower/Raise command for
follower transformer 5 in
the Master/Follower opera-
tion mode
BLKD_I_LOD BOOLEAN Indication of over current
blocking
BLKD_U_UN BOOLEAN Indication of under voltage
blocking
RNBK_U_OV BOOLEAN Indication of raise voltage
runback
BLKD_I_CIR BOOLEAN Indication of high circulating
current blocking
BLKD_LTCBLK BOOLEAN Indication of external block-
ing
ALARM BOOLEAN Alarm status
PAR_FAIL BOOLEAN Parallel failure detected
PARALLEL BOOLEAN Parallel or single operation
AUTO BOOLEAN Auto/Manual indication
MASTER BOOLEAN Master indication
TAP_DIFF BOOLEAN Tap difference between fol-
lower and master
REV_REG BOOLEAN Reverse regulation
9.10.8 OL5ATCC Settings
1MRS759142 F
Control functions
REX640
Technical Manual
1723