9.11.9.2 PASANCR Output signals
Table 1593: PASANCR Output signals
Name Type Description
RAISE_OWN BOOLEAN Increase coil current
LOWER_OWN BOOLEAN Decrease coil current
FIXCOIL BOOLEAN Status information to control
fixed coil on/off
OP_FIXCOIL BOOLEAN Command to disconnect fix
coil
CL_FIXCOIL BOOLEAN Command to connect fix coil
RESISTOR BOOLEAN Status information to control
parallel current rising resistor
on/off
OP_RESISTOR BOOLEAN Command to disconnect par-
allel current rising resistor
CL_RESISTOR BOOLEAN Command to connect parallel
current rising resistor
ALARM BOOLEAN General alarm indication
MOT_ALARM BOOLEAN Motor alarm: no detected coil
movement
POT_ALARM BOOLEAN Potentiometer alarm
EARTH_FAULT BOOLEAN Earth-fault indication
HIF BOOLEAN High impedance fault indica-
tion
TUNING_ACT BOOLEAN Automatic tuning procedure
ongoing
TUNING_SUC BOOLEAN Tuning successful
9.11.10 PASANCR Settings
Table 1594: PASANCR Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Compensation
mode
1=Absolute
2=Relative
1=Absolute Compensation de-
gree in absolute
amperes or relative
to the resonance
point
Detuning level -100...100 A 1 0 Detuning level in
amperes
Detuning level Rl -100.0...100.0 % 0.1 0.0 Detuning level in
percent
V Res change level 0.0...1000.0 %Uref 0.1 10.0 Zero-sequence volt-
age change thresh-
old as percent of
reference voltage
V Res Meas mode
1=Amplitude
2=Phasor Uo trigger based
on amplitude or
Table continues on the next page
1MRS759142 F Control functions
REX640
Technical Manual
1749