200 °C
-40 °C
Input mode
”Pt100”
Input
AI_VAL
Value unit
”Degrees celsius”
Figure 69: Pt100 scaling function
Scaling example 2
Input mode
is set to –20...20 mA that is used for tap position information fed from
the tap changer. The tap positions are between –36...36. Thus, the scaling setting
Value minimum
is set to "–36" and
Value maximum
is set to "36". These settings
apply the input scaling to the output. In the tap position case, the
Value unit
should
be set to "Dimensionless".
Value unit
Value minimum
Value maximum
”Dimensionless”
4 mA
Input mode
”-20..20mA”
36
-36
20 mA
Input
AI_VAL
Input minimum Input maximum
Figure 70: Tap changer position from mA input
Scaling example 3
When
Input mode
is set to "Resistance", the output can be scaled as desired. For
example, the desired function output is a ratio in a function of resistance. If the
input resistance varies between 100...1600 ohms,
Input minimum
is set to "100" and
Input maximum
is set to "1600". As the wanted output should be in percents, the
setting
Value unit
is set to "Dimensionless". When
Input mode
is set to "Resistance",
output scaling is enabled. Thus,
Value minimum
is set to "0" and
Value maximum
is set to "100". These settings allow the input values to be scaled as a ratio of the
resistance range.
1MRS759142 F
Basic functions
REX640
Technical Manual
175