Name Type Default Description
RST_LKOUT BOOLEAN 0=False Reset lockout
RST_ALARM BOOLEAN 0=False Reset traveling time
alarms
9.12.7.2 HSABTC Output signals
Table 1609: HSABTC Output signals
Name Type Description
READY BOOLEAN Ready for transfer
NOT_READY BOOLEAN Not ready for transfer
TR_RUNNING BOOLEAN Transfer is in running state
NOT_IDLE BOOLEAN Transfer is not in idle state
LOCKOUT BOOLEAN Transfer lockout status
FAST_READY BOOLEAN Ready for fast transfer
OPEN_CB1 BOOLEAN Open command for feeder 1
breaker
CLOSE_CB1 BOOLEAN Close command for feeder 1
breaker
OPEN_CB2 BOOLEAN Open command for feeder 2
breaker
CLOSE_CB2 BOOLEAN Close command for feeder 2
breaker
OPR_LOADSHED BOOLEAN Activate load shedding
CB_DECOUPL BOOLEAN CB decoupling activated
COMPL_FAST BOOLEAN Fast transfer complete
COMPL_FBBM BOOLEAN Fast break before make
transfer complete
COMPL_1ST_PH BOOLEAN First phase coincidence
transfer complete
COMPL_RES BOOLEAN Residual voltage based trans-
fer complete
COMPL_TDLY BOOLEAN Time delayed based transfer
complete
TR_CANCEL BOOLEAN Transfer cancelled
FRQDIFF_FAIL BOOLEAN Frequency difference is not in
range for fast transfer
ANGDIFF_FAIL BOOLEAN Phase angle difference is not
in range for fast transfer
GRAD_FAIL BOOLEAN Frequency gradient over per-
missible for 1st phase trans-
fer
Table continues on the next page
1MRS759142 F Control functions
REX640
Technical Manual
1799