Parameter Values (Range) Unit Step Default Description
Opening time of
CB1
0...200 ms 1 40 Opening time of
the breaker feeder1
Opening time of
CB2
0...200 ms 1 40 Opening time of
the breaker feeder2
Close cmd delay
time
0...200 ms 1 0 Breaker close com-
mand delay time
Load shedding
mode
1=None
2=Instantaneous
3=Voltage based
4=Time based
1=None Load shedding op-
eration mode
Enable decoupling
1=Off
2=Transfer based
3=CB man close
4=Both
1=Off Enable circuit
breaker decoupling
Decoupling delay 50...200000 ms 1 1000 Circuit breaker de-
coupling delay
9.12.9 HSABTC Monitored data
Table 1614: HSABTC Monitored data
Name Type Values (Range) Unit Description
STATUS Enum
0=Off
1=Ready - sync
2=Ready - no sync
3=Not ready - sync
4=Not ready - no sync
5=Transfer running
6=Not defined
Transfer status
FRQ_DIFF FLOAT32 -30.00...30.00 Hz Frequency difference
between standby feed-
er and busbar
ANG_DIFF_1 FLOAT32 -180.0...180.0 deg Angle difference be-
tween feeder 1 and bus-
bar
ANG_DIFF_2 FLOAT32 -180.0...180.0 deg Angle difference be-
tween feeder 2 and bus-
bar
CLS_T_CB1 FLOAT32 0.0...10000.0 ms Measured close time for
circuit breaker of feeder
1
CLS_T_CB2 FLOAT32 0.0...10000.0 ms Measured close time for
circuit breaker of feeder
2
OPN_T_CB1 FLOAT32 0.0...10000.0 ms Measured open time for
circuit breaker of feeder
1
OPN_T_CB2 FLOAT32 0.0...10000.0 ms Measured open time for
circuit breaker of feeder
2
ACT_CLS_T_CB1 FLOAT32 0.0...10000.0 ms Active close time for
circuit breaker of feeder
1
ACT_CLS_T_CB2 FLOAT32 0.0...10000.0 ms Active close time for
circuit breaker of feeder
2
Table continues on the next page
1MRS759142 F Control functions
REX640
Technical Manual
1803