Parameter Values (Range) Unit Step Default Description
correction of an
external voltage
transformer
Amplitude Corr B 0.9000...1.1000 0.0001 1.0000 Phase B Voltage
phasor magnitude
correction of an
external voltage
transformer
Amplitude Corr C 0.9000...1.1000 0.0001 1.0000 Phase C Voltage
phasor magnitude
correction of an
external voltage
transformer
Angle Corr A -8.0000...8.0000 deg 0.0001 0.0000 Phase A Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
Angle Corr B -8.0000...8.0000 deg 0.0001 0.0000 Phase B Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
Angle Corr C -8.0000...8.0000 deg 0.0001 0.0000 Phase C Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
Table 132: UTVTR Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Frequency adaptivi-
ty
0=Disable
1=Enable
2=Main frequency
source
3=Backup frequen-
cy source
0=Disable Frequency adaptivi-
ty selection
Table 133: UTVTR Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Primary voltage 0.100...800.000 kV 0.001 11.547 Primary voltage
Secondary voltage 57...240 V 1 100 Secondary voltage
Amplitude Corr 0.9000...1.1000 0.0001 1.0000 Amplitude correc-
tion
Angle correction -8.0000...8.0000 deg 0.0001 0.0000 Angle correction
factor
Table 134: UTVTR Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Frequency adaptivi-
ty
0=Disable
1=Enable
0=Disable Frequency adaptivi-
ty selection
Basic functions 1MRS759142 F
202 REX640
Technical Manual