Parameter Values (Range) Unit Step Default Description
Pulse time 7 0...3600000 ms 1 0 Pulse time
Pulse time 8 0...3600000 ms 1 0 Pulse time
3.20.2.6 Monitored data
Table 208: PTGAPC Monitored data
Name Type Values (Range) Unit Description
T_LEFT1 FLOAT32 0...3600 s Time left 1
T_LEFT2 FLOAT32 0...3600 s Time left 2
T_LEFT3 FLOAT32 0...3600 s Time left 3
T_LEFT4 FLOAT32 0...3600 s Time left 4
T_LEFT5 FLOAT32 0...3600 s Time left 5
T_LEFT6 FLOAT32 0...3600 s Time left 6
T_LEFT7 FLOAT32 0...3600 s Time left 7
T_LEFT8 FLOAT32 0...3600 s Time left 8
3.20.2.7 Technical data
Table 209: PTGAPC Technical data
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
3.20.2.8 Technical revision history
Table 210: PTGAPC Technical revision history
Product connectivity
level
Technical revision Change
PCL2 E Changed the
Pulse time
step to 1 ms
3.20.3 Daily timer DTMGAPC (ANSI DTM)
3.20.3.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Daily timer DTMGAPC DTM DTM
1MRS759142 F Basic functions
REX640
Technical Manual
237