If the result of AIn_VALUE multiplied by the Scale ratio n setting exceeds
the analog output range, AOn_VALUE shows the minimum or maximum
value, according to analog value range.
3.20.10.4 Signals
Table 240: SCA4GAPC Input signals
Name Type Default Description
AI1_VALUE FLOAT32 0.0 Analog input value of
channel 1
AI2_VALUE FLOAT32 0.0 Analog input value of
channel 2
AI3_VALUE FLOAT32 0.0 Analog input value of
channel 3
AI4_VALUE FLOAT32 0.0 Analog input value of
channel 4
Table 241: SCA4GAPC Output signals
Name Type Description
AO1_VALUE FLOAT32 Analog value 1 after scaling
AO2_VALUE FLOAT32 Analog value 2 after scaling
AO3_VALUE FLOAT32 Analog value 3 after scaling
AO4_VALUE FLOAT32 Analog value 4 after scaling
3.20.10.5 Settings
Table 242: SCA4GAPC settings
Parameter Values (Range) Unit Step Default Description
Scale ratio 1 0.001...1000.000 0.001 1.000 Scale ratio for analog value 1
Scale ratio 2 0.001...1000.000 0.001 1.000 Scale ratio for analog value 2
Scale ratio 3 0.001...1000.000 0.001 1.000 Scale ratio for analog value 3
Scale ratio 4 0.001...1000.000 0.001 1.000 Scale ratio for analog value 4
3.20.11 16 settable real values SETRGAPC
3.20.11.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
16 settable real values SETRGAPC SETRGAPC SETRGAPC
1MRS759142 F Basic functions
REX640
Technical Manual
255