Parameter Values (Range) Unit Step Default Description
Curve parameter B 0.0000...0.7120 0.0001 0.1217 Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00 0.01 2.00 Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00 0.01 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 0.1 1.0 Parameter E for
customer program-
mable curve
Table 519: EFHPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate
time
20...60000 ms 1 20 Minimum operate
time for IDMT
curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
EFIPTOC Settings
Table 520: EFIPTOC Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 1.00...40.00 xIn 0.01 1.00 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Operate delay time 20...300000 ms 10 20 Operate delay time
Table 521: EFIPTOC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 522: EFIPTOC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
4.2.1.11 Monitored data
EFLPTOC Monitored data
Table 523: EFLPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
EFLPTOC Enum
1=on
2=blocked
3=test
Status
1MRS759142 F Protection functions
REX640
Technical Manual