ABB RELION REX640 - 4.2.7.12 Technical data; 4.2.8 Third harmonic based stator earth-fault protection H3 EFPSEF (ANSI 64 TN); 4.2.8.1 Identification; 4.2.8.2 Function block

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Values (Range) Unit Description
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operat-
ing angle and charac-
teristic angle
RES_POWER FLOAT32 -160.000...160.000 xPn Calculated residual ac-
tive power
WPWDE Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.2.7.12 Technical data
Table 601: WPWDE Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f
n
±2 Hz
Current and voltage:
±1.5% of the set value or ±0.002 × I
n
Power:
±3% of the set value or ±0.002 × P
n
Start time
1, 2
Typically 63 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Operate time accuracy in definite time mode
3
±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode ±5.0% of the set value or ±20 ms
Suppression of harmonics -50 dB at f = n × f
n
, where n = 2,3,4,5,…
4.2.8 Third harmonic based stator earth-fault protection
H3EFPSEF (ANSI 64TN)
4.2.8.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Third harmonic-based stator earth-
fault protection
H3EFPSEF dUo>/Uo3H 64TN
1
Io varied during the test, U
o
= 1.0 × U
n
= phase-to-earth voltage during earth fault in compensa-
ted or unearthed network, the residual power value before fault = 0.0 pu, f
n
= 50 Hz, results based
on statistical distribution of 1000 measurements.
2
Includes the delay of the signal output contact.
3
Start time of the function also included.
1MRS759142 F Protection functions
REX640
Technical Manual
541