Parameter Values (Range) Unit Step Default Description
6=6:16bit FrzCnt
evt&time
6=16 bit frz counter
event with time.
Default Var Obj 30
1=1:32bit AI
2=2:16bit AI
3=3:32bit AI noflag
4=4:16bit AI noflag
5=5:AI float
6=6:AI double
5=5:AI float 1=32 bit AI; 2=16 bit
AI; 3=32 bit AI with-
out flag; 4=16 bit AI
without flag; 5=AI
float; 6=AI double.
Default Var Obj 32
1=1:32bit AI evt
2=2:16bit AI evt
3=3:32bit AI
evt&time
4=4:16bit AI
evt&time
5=5: float AI evt
6=6:double AI evt
7=7:float AI
evt&time
8=8:double AI
evt&time
7=7:float AI
evt&time
1=32 bit AI event;
2=16 bit AI event;
3=32 bit AI event
with time; 4=16 bit
AI event with time;
5=float AI event;
6=double AI event;
7=float AI event
with time; 8=dou-
ble AI event with
time.
Default Var Obj 40
1=1:32bit AO
2=2:16bit AO
3=3:AO float
4=4:AO double
2=2:16bit AO 1=32 bit AO; 2=16
bit AO; 3=AO float;
4=AO double.
Default Var Obj 42
1=1:32bit AO evt
2=2:16bit AO evt
3=3:32bit AO
evt&time
4=4:16bit AO
evt&time
5=5:float AO evt
6=6:double AO evt
7=7:float AO
evt&time
8=8:double AO
evt&time
4=4:16bit AO
evt&time
1=32 bit AO event;
2=16 bit AO event;
3=32 bit AO event
with time; 4=16 bit
AO event with time;
5=float AO event;
6=double AO event;
7=float AO event
with time; 8=dou-
ble AO event with
time.
An In Evt Mod
0=0:SOE
1=1:Most Recent
0=0:SOE Analog Input Event
Mode - 0: Sequence
of Events, 1: Most
Recent
Prtl Customization 0...2147483647 1 0 Customization pa-
rameter. Please, re-
fer to the protocol
manual.
3.1.20 DNP 3.0 Secure settings
Table 26: Non group settings
Parameter Values (Range) Unit Step Default Description
Protocol Security
Mode
1=App. authentica-
tion
0=Off Protocol Security
Mode - 0: Off; 1:
Aplication authenti-
cation; 2: TLS and
Table continues on the next page
1MRS759142 F Basic functions
REX640
Technical Manual
73