HIAPDIF Settings
Table 703: HIAPDIF Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operate value 1.0...200.0 %In 1.0 5.0 Operate value, per-
centage of the
nominal current
Minimum operate
time
20...300000 ms 10 20 Minimum operate
time
Table 704: HIAPDIF Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 705: HIAPDIF Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
HIBPDIF Settings
Table 706: HIBPDIF Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operate value 1.0...200.0 %In 1.0 5.0 Operate value, per-
centage of the
nominal current
Minimum operate
time
20...300000 ms 10 20 Minimum operate
time
Table 707: HIBPDIF Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 708: HIBPDIF Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
HICPDIF Settings
Table 709: HICPDIF Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operate value 1.0...200.0 %In 1.0 5.0 Operate value, per-
centage of the
nominal current
Minimum operate
time
20...300000 ms 10 20 Minimum operate
time
Table 710: HICPDIF Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
1=on Operation Off / On
1MRS759142 F Protection functions
REX640
Technical Manual
785