Table 37: Protocol write access in the protection relay
Parameter Options Description
Configuration/Authorization/Net-
work1/FTP write access
Off FTP write access denied for
Network 1
On (Default) FTP write access allowed for
Network 1
Configuration/Authorization/Net-
work1/MMS write access
Off IEC 61850 MMS write access
denied for Network 1
On (Default) IEC 61850 MMS write access
allowed for Network 1
Configuration/Authorization/Net-
work1/HTTPS write access
Off HTTPS write access denied
for Network 1
On (Default) HTTPS write access allowed
for Network 1
Configuration/Authorization/Net-
work2/FTP write access
Off FTP write access denied for
Network 2
On (Default) FTP write access allowed for
Network 2
Configuration/Authorization/Net-
work2/MMS write access
Off IEC 61850 MMS write access
denied for Network 2
On (Default) IEC 61850 MMS write access
allowed for Network 2
Configuration/Authorization/Net-
work2/HTTPS write access
Off HTTPS write access denied
for Network 2
On (Default) HTTPS write access allowed
for Network 2
Configuration/Authoriza-
tion/HMI/FTP write access
Off FTP write access denied for
the HMI port
On (Default) FTP write access allowed for
the HMI port
Configuration/Authoriza-
tion/HMI/MMS write access
Off IEC 61850 MMS write access
denied for the HMI port
On (Default) IEC 61850 MMS write access
allowed for the HMI port
PCM600 is using FTP or FTPS protocol to communicate with the
protection relay. If the FTP write access is disabled for a network PCM600
functionality is limited to support read operations only from Disturbance
handling, Event viewer and Parameter Setting.
Enabling Network 2 IP address requires additional configuration in
PCM600 to define IEC 61580 subnetworks. This configuration is done
via Ethernet Configuration and IEC 61850 Configuration in PCM600.