EasyManua.ls Logo

ABB RELION REX640 - Example calculations for overexcitation protection

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
to be considered in a proper overexcitation protection of the transformer. Also,
measurement for the voltage must not be taken from any winding where OLTC is
located.
It is assumed that overexcitation is a symmetrical phenomenon caused by events
such as loss-of-load. A high phase-to-earth voltage does not mean overexcitation.
For example, in an unearthed power system, a single phase-to-earth fault means
high voltages of the healthy two phases to earth but no overexcitation on any
winding. The phase-to-phase voltages remain essentially unchanged. An important
voltage to be considered for the overexcitation is the voltage between the two ends
of each winding.
Example calculations for overexcitation protection
Example 1
Nominal values of the machine
Nominal phase-to-phase voltage (U
n
) 11000 V
Nominal phase current (I
n
) 7455 A
Nominal frequency (f
n
) 50 Hz
Leakage reactance (X
leak
) 20% or 0.2 pu
Measured voltage and load currents of the machine
Phase A-to-phase B voltage (U
AB
) 11500∠0° V
Phase A current (I
A
) 5600∠-63.57° A
Phase B current (I
B
) 5600∠176.42° A
Measured frequency (f
m
) 49.98 Hz
The setting
Voltage Max Cont
100%
The setting
Voltage selection
phase-to-phase
The setting
Phase supervision
A or AB
The pu leakage reactance X
leakPU
is converted to ohms.
X X
U
I
Ohms
leak leakPU
n
n
=
=
=
3
0 2
11000
7455 3
0 170378. .
(Equation 251)
The internal induced voltage E of the machine is calculated.
E U I I jX
AB A B leak
= + ( ) ( )
(Equation 252)
E = 11500∠0°+ (5600∠-63.57°- 5600∠176.42°) · (0.170378∠90°) = 12490 V
The excitation level M of the machine is calculated.
Protection functions
1MRS759142 F
894 REX640
Technical Manual

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals