Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by bad
data quality bits or GOOSE communication failure. See IEC 61850 engineering guide
for details.
The OUT output passes the received GOOSE value for the application. Default value
(0) is used if VALID output indicates invalid status. The IN input is defined in the
GOOSE configuration and can always be seen in SMT sheet.
Settings
3.14.1 GOOSERCV_BIN function block
3.14.1.1 Function block
GUID-44EF4D6E-7389-455C-BDE5-B127678E2CBC V1 EN
Figure 48: Function block
3.14.1.2 Functionality
The GOOSERCV_BIN function is used to connect the GOOSE binary inputs to the
application.
3.14.1.3 Signals
Table 52: GOOSERCV_BIN Output signals
Name
Type Description
OUT BOOLEAN Output signal
VALID BOOLEAN Output signal
3.14.2 GOOSERCV_DP function block
3.14.2.1 Function block
GUID-63C0C3EE-1C0E-4F78-A06E-3E84F457FC98 V1 EN
Figure 49: Function block
1MRS758755 A Section 3
Basic functions
REC615 and RER615 107
Technical Manual