3.15.3.2 Functionality
The QTY_GOOSE_COMM function block evaluates the peer device communication
status from the quality bits of the input signal and passes it as a Boolean signal to the
application.
The IN input can be connected to any GOOSE application logic output signal, for
example, GOOSERCV_BIN.
The OUT output indicates the communication status of the GOOSE function block.
When the output is in the true (1) state, the GOOSE communication is active. The
value false (0) indicates communication timeout.
3.15.3.3 Signals
Table 64: QTY_GOOSE_COMM Input signals
Name Type Default Description
IN Any 0 Input signal
Table 65: QTY_GOOSE_COMM Output signals
Name
Type Description
COMMVALID BOOLEAN Output signal
3.15.4 T_HEALTH function block
3.15.4.1 Function block
GUID-B5FCAE66-8026-4D5F-AC38-028E5A8171BB V1 EN
Figure 59: Function block
3.15.4.2 Functionality
The T_HEALTH function evaluates enumerated data of “Health” data attribute. This
function block can only be used with GOOSE.
The IN input can be connected to GOOSERCV_ENUM function block, which is
receiving the LD0.LLN0.Health.stVal data attribute sent by another device.
The outputs OK, WARNING and ALARM are extracted from the enumerated input
value. Only one of the outputs can be active at a time. In case the
Section 3 1MRS758755 A
Basic functions
114 REC615 and RER615
Technical Manual