3.16.9.3 Signals
Table 158: MVI4GAPC Input signals
Name
Type Default Description
IN1 INT32 0 Integer input value 1
IN2 INT32 0 Integer input value 2
IN3 INT32 0 Integer input value 3
IN4 INT32 0 Integer input value 4
Table 159: MVI4GAPC Output signals
Name Type Description
OUT1 INT32 Integer output value 1
OUT2 INT32 Integer output value 2
OUT3 INT32 Integer output value 3
OUT4 INT32 Integer output value 4
3.16.10 Analog value scaling SCA4GAPC
3.16.10.1 Function block
AI1_VALUE
AI2_VALUE AO2_VALUE
AI3_VALUE
AI4_VALUE
AO3_VALUE
AO4_VALUE
AO1_VALUE
SCA4GAPC
GUID-9D830A50-37F1-4478-B458-9C90742ECA54 V1 EN
Figure 96: Function block
3.16.10.2 Functionality
The analog value scaling function SCA4GAPC is used for scaling the analog value. It
allows creating events from analog values.
The analog value received via the AIn_VALUE input is scaled with the Scale ratio n
setting. The scaled value is available on the AOn_VALUE output.
Analog input range is from -10000.0 to 10000.0.
1MRS758755 A Section 3
Basic functions
REC615 and RER615 151
Technical Manual